DN-6726:D • 4/13/2012 — Page 1 of 2
NBG-12LX
Addressable Manual Pull Station
Intelligent/Addressable Devices
DN-6726:D • H-240
The NBG-12LX
Addressable Ma
nual Pull Station
6
6
4
3
c
o
v
1
.
jp
g
‘
General
The Notifier NBG-12LX is a state-of-the-art, dual-action (i.e.,
requires two motions to activate the station) pull station that
includes an addressable interface for any Notifier intelligent
control panel except FireWarden series panels, and the NSP-
25 panel. Because the NBG-12LX is addressable, the control
panel can display the exact location of the activated manual
station. This leads fire personnel quickly to the location of the
alarm.
Features
• Maintenance personnel can open station for inspection and
address setting without causing an alarm condition.
• Built-in bicolor LED, which is visible through the handle of
the station, flashes in normal operation and latches steady
red when in alarm.
• Handle latches in down position and the word “ACTIVATED”
appears to clearly indicate the station has been operated.
• Captive screw terminals wire-ready for easy connection to
SLC loop (accepts up to 12 AWG/3.25 mm² wire).
• Can be surface mounted (with SB-10 or SB-I/O) or semi-
flush mounted. Semi-flush mount to a standard single-
gang, double-gang, or 4" (10.16 cm) square electrical box.
• Smooth dual-action design.
• Meets ADAAG controls and operating mechanisms guide-
lines (Section 4.1.3[
13]); meets ADA requirement for 5 lb.
maximum activation force.
• Highly visible.
• Attractive shape and textured finish.
• Key reset.
• Includes Braille text on station handle.
• Optional trim ring (BG12TR).
• Meets UL 38, Standard for Manually Actuated Signaling
Boxes.
• Up to 99 NBG-12LX stations per loop on CLIP protocol
loops.
• Up to 159 NBG-12LX stations per loop on FlashScan® pro-
tocol loops.
• Dual-color LED blinks green to indicate normal on
FlashScan® systems.
Construction
Shell, door, and handle are molded of durable polycarbonate
material with a textured finish.
Specifications
•
Shipping Weight:
9.6 oz. (272.15 g)
•
Normal operating voltage:
24 VDC.
•
Maximum SLC loop voltage:
28.0 VDC.
•
Maximum SLC standby current:
375 A.
•
Maximum SLC alarm current:
5 mA.
•
Temperature Range:
32°F to 120°F (0°C to 49°C)
•
Relative Humidity:
10% to 93% (noncondensing)
•
For use indoors in a dry location
Installation
The NBG-12LX will mount semi-flush into a single-gang, dou-
ble-gang, or standard 4" (10.16 cm) square electrical outlet
box, or will surface mount to the model SB-10 or SB-I/O sur-
face backbox. If the NBG-12LX is being semi-flush mounted,
then the optional trim ring (BG12TR) may be used. The
BG12TR is usually needed for semi-flush mounting with 4"
(10.16 cm) or double-gang boxes (not with single-gang boxes).
Operation
Pushing in, then pulling down on the handle causes it to latch
in the down/activated position. Once latched, the word “ACTI-
VATED” (in bright yellow) appears at the top of the handle,
while a portion of the handle protrudes from the bottom of the
station. To reset the station, simply unlock the station with the
key and pull the door open. This action resets the handle; clos-
ing the door automatically resets the switch.
Each manual station, on command from the control panel,
sends data to the panel representing the state of the manual
switch. Two rotary decimal switches allow address settings
(1 – 159 on FlashScan® systems, 1 – 99 on CLIP systems).
Architectural/Engineering
Specifications
Manual Fire Alarm Stations shall be non-coded, with a key-
operated reset lock in order that they may be tested, and so
designed that after actual Emergency Operation, they cannot
be restored to normal except by use of a key. An operated sta-
tion shall automatically condition itself so as to be visually
detected as activated. Manual stations shall be constructed of
red-colored polycarbonate material with clearly visible operat-
ing instructions provided on the cover. The word FIRE shall
appear on the front of the stations in white letters, 1.00 inches
(2.54 cm) or larger. Stations shall be suitable for surface
mounting on matching backbox SB-10 or SB-I/O; or semi-flush
mounting on a standard single-gang, double-gang, or
Page 2 of 2 — DN-6726:D • 4/13/2012
NOTIFIER® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2012 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Made in the U.S. A.
4" (10.16 cm) square electrical box, and shall be installed
within the limits defined by the Americans with Disabilities Act
(ADA) or per national/local requirements. Manual Stations
shall be Underwriters Laboratories listed.
Manual stations shall connect with two wires to one of the con-
trol panel SLC loops. The manual station shall, on command
from the control panel, send data to the panel representing the
state of the manual switch. Manual stations shall provide
address setting by use of rotary decimal switches.
The loop poll LED shall be clearly visible through the front of
the station. The LED shall flash while in the normal condition,
and stay steadily illuminated when in alarm.
Product Line Information
NBG-12LX:
Dual-action addressable pull station. Includes key
locking feature. (Listed for Canadian and non-Canadian appli-
cations.)
NBG-12LXSP:
Spanish/English labelled version.
NBG-12LXP:
Portuguese labelled version.
SB-10:
Surface backbox; metal.
SB-I/O:
Surface backbox; plastic.
BG12TR:
Optional trim ring.
17021:
Keys, set of two.
NY-Plate:
New York City trim plate.
Agency Listings and Approvals
In some cases, certain modules or applications may not be
listed by certain approval agencies, or listing may be in pro-
cess. Consult factory for latest listing status.
•
UL/ULC Listed:
S692 (listed for Canadian and non-Cana-
dian applications).
•
MEA:
67-02-E.
•
CSFM:
7150-0028:0199.
•FDNY:
COA #6085 (NFS2-640), COA #6098 (NFS2-3030).
•
BSMI:
CI313066760047.
• U.S. Coast Guard.
• Lloyd’s Register.
• FM Approved.
Patented:
U.S. Patent No. D428,351; 6,380,846; 6,314,772;
6,632,108.
PDF document for